HYDROTHANE TR is a high-build, elastomeric, polyurethane-based waterproofing membrane extended with coal tar for enhanced elasticity and chemical resistance in harsh environments. HYDROTHANE TR cures into a seamless, flexible layer with excellent adhesion to concrete, plaster, masonry, and other substrates, ideal for foundations, wet areas, and industrial facilities. The membrane is self-priming with vapor permeability to allow substrate breathing, while offering superior crack-bridging ability and chemical resistance against detergents, brackish water, and saltwater. HYDROTHANE TR is easy to apply by manual tools, exhibits outstanding thermal stability suited for Middle Eastern climates, and allows quick, simple repairs if the membrane is damaged.
Hydrothane TR is a single component, ready to use membrane applied by roller, trowel, brush or spray, normally in two coats.
Summary of the method in the Hydrothane Tr Technical Data Sheet. Always follow the full TDS on site.
| Standard | Title | Referenced for |
|---|---|---|
| ASTM D412 | Standard Test Methods for Vulcanized Rubber and Thermoplastic Elastomers—Tension | Tensile strength (>1.5 N/mm²) and elongation (>600%) |
| ASTM D624 | Standard Test Method for Tear Strength of Conventional Vulcanized Rubber and Thermoplastic Elastomers | Tear resistance |
| ASTM D2240 | Standard Test Method for Rubber Property—Durometer Hardness | Shore A hardness (50) |
| ASTM D4541 | Standard Test Method for Pull-Off Strength of Coatings Using Portable Adhesion Testers | Adhesion to concrete (>1.0 N/mm²) |
| ASTM C1305 | Standard Test Method for Crack Bridging Ability of Liquid-Applied Waterproofing Membrane | Crack bridging (>2 mm) |
| ASTM E96 | Standard Test Methods for Water Vapor Transmission of Materials | Water vapor transmission (>0.31 g/h/m²) |
| ASTM C836 | Standard Specification for High Solids Content, Cold Liquid-Applied Elastomeric Waterproofing Membrane for Use with Separate Wearing Course | Listed in the TDS |
Standards and test methods as referenced in the Hydrothane Tr Technical Data Sheet. Values in the TDS are typical laboratory results under standard conditions.
Coverage is 1.4 kg per m² at 1.0 mm dry film thickness. By roller or brush, apply two coats at approx. 0.65 kg/m² per coat.
Touch dry is 10 hours and full dry is 7 days at 25°C. Do not apply tile adhesive until the membrane has cured.
Application temperature is +5°C to +40°C, with best results between 5°C and 35°C. Service temperature is -5°C to 75°C.
Normally no; it is self-priming. Porous surfaces need priming with Hydrothane TR diluted with 10% Armosolvent to reduce blistering from entrapped air.
It is supplied in 20 kg pails. Shelf life is minimum 6 months from production in unopened original packing, stored dry at +15°C to 25°C away from direct sunlight and high humidity.